VICTOR EQUIPMENT CO -- 0056-1296 MAPP GAS (0916-0009) -- 6830-00F030990
=====================  Product Identification  =====================

Product ID:0056-1296 MAPP GAS (0916-0009)
MSDS Date:01/01/1991
FSC:6830
NIIN:00F030990
=== Responsible Party ===
Company Name:VICTOR EQUIPMENT CO
Address:AIRPORT RD
Box:1007
City:DENTON
State:TX
ZIP:76202
Country:US
Info Phone Num:817-566-2000/FAX 817-381-1222
Emergency Phone Num:214-590-5000
CAGE:63026
=== Contractor Identification ===
Company Name:VICTOR EQUIPMENT CO
Address:2800 AIRPORT RD
Box:1007
City:DENTON
State:TX
ZIP:76202
Country:US
Phone:940-566-2000
CAGE:63026

=============  Composition/Information on Ingredients  =============

Ingred Name:METHYL ACETHYLENE					       
			       IC=INTENDED CHANGES
CAS:74-99-7
RTECS #:UK4250000
Fraction by Wt: 44%
Other REC Limits:1000 PPM=IC
OSHA PEL:1,650 MG/CUM
ACGIH TLV:1640 MG/CUM

Ingred Name:HYDROCARBONS, C3-4, LIQUIFIED PETROLEUM GAS
CAS:68476-40-4
Fraction by Wt: 56%
OSHA PEL:1000 PPM
ACGIH TLV:1000 PPM

=====================  Hazards Identification  =====================

Routes of Entry: Inhalation:YES  Skin:YES  Ingestion:YES
Reports of Carcinogenicity:NTP:NO    IARC:NO	OSHA:NO
Health Hazards Acute and Chronic:CNS DEPREESION, IRRITANT. INHALATION:
    ASPHYXIANT. EYES: IRRITANT, BLINDNESS. HIGH CONCENTRATIONS W/OUT
    OXYGEN TO THE LUNGS WILL CAUSE POSSIBLE DEATH. SKIN: FROSTBITE,
    IRRITATION.
Explanation of Carcinogenicity:NONE
Effects of Overexposure:INHALATION: EXCITEMENT, DISORIENTATION,
    UNCONSCIOUSNESS.

=======================  First Aid Measures  =======================

First Aid:SKIN: REMOVE CONTAMINATED CLOTHING & FLUSH AFFECTED AREAS
    W/LUKEWARM WATER. DON'T USE HOT WATER. INHALATION: REMOVE TO FRESH
    AIR. GIVE CPR/OXYGEN IF NECESSARY. TREAT SYMPTOMATIC & SUPPORTIVE.
    OBTAIN M EDICAL ATTENTION IN ALL CASES.

=====================  Fire Fighting Measures  =====================

Flash Point Method:CC
Flash Point:144F
Lower Limits:3.0%
Upper Limits:11.0%
Extinguishing Media:WATER FOG, DRY CHEMICAL FOAM
Fire Fighting Procedures:DON'T EXTINGUISH. KEEP CYLINDER COOL W/WATER
    FOG. IF FLAME IS EXTINGUISHED, REMOVE IGNITION SOURCES. VENTILATE.
    USE SELF CONTAINED BREATHING APPARATUS.
Unusual Fire/Explosion Hazard:GAS IS HEAVIER THAN AIR & MAY TRAVEL A
    CONSIDERABLE DISTANCE TO A SOURCE OF IGNITION. FLAMMABLE GAS. GAS
    PRESENTS DANGER OF EXPLOSION/FIRE.

==================  Accidental Release Measures  ==================

Spill Release Procedures:EVACUATE ALL PERSONNEL FROM AFFECTED AREA. USE
    APPROPRIATE PROTECTIVE EQUIPMENT. IF LEAK IN EQUIPMENT, BE CERTAIN
    TO PURGE PIPING W/INERT GAS PRIOR TO ATTEMPTING REPAIRS. IF LEAK IS
    IN CONTAINER/CONTA INER VALVE, CONTACT THE CLOSEST SUPPLIER
    LOCATION.

======================	Handling and Storage  ======================

Handling and Storage Precautions:STORE IN COOL/DRY AREA. STORE
    TEMPERATURES <130F. CYLINDER SHOULD BE STORED UPRIGHT & FIRMLY
    SECURED. FULL/EMPTY CONTAINERS SHOULD BE SEGREGATED.
Other Precautions:USE IN VENTILATED AREAS. VALVE CAPS MUST REMAIN IN
    PLACE. DON'T DRAG/SLIDE/ROLL CYLINDERS. DON'T HEAT CYLINDER,
    INCREASES DISCHARGE RATE OF PRODUCT. KEEP AWAY FROM IGNITION
    SOURCES.

=============  Exposure Controls/Personal Protection  =============

Respiratory Protection:USE AIR SUPPLIED RESPIRATOR FOR EXTREME CONFINED
    AREAS WHEN WELDING/CUTTING/BRAZING.
Ventilation:LOCAL EXHAUST/MECHANICAL WHEN WELDING/CUTTING IN CONFINED
    SPACES.
Protective Gloves:LEATHER
Eye Protection:SAFETY GLASSES W/FILTER LENSES #4/DARKER
Other Protective Equipment:LEATHER APRON WHEN WELDING/CUTTING/BRAZING
Supplemental Safety and Health
SPECIFIC GRAVITY LIQUID: 0.571. LIQUID DENSITY: 4.68 LBS/GAL. ANY LEAKS
    OF MAPP GAS PRESENT GREAT DANGER OF EXPLOSION OR FIRE. KEEP ALL
    SOURCES OF IGNITION AWAY. ELECTRICAL EQUIPMENT SHOULD BE NON-SPA
    RKING/EXPLOSION PROOF. CYLINDERS SHOULDN'T BE REFILLED EXCEPT BY
    QUALIFIED PRODUCERS OF COMPRESSED GASES.

==================  Physical/Chemical Properties  ==================

Boiling Pt:B.P. Text:-54 TO -10F
Melt/Freeze Pt:M.P/F.P Text:-184F
Vapor Pres:97 PSIG
Vapor Density:0.110
Spec Gravity:1.48
Solubility in Water:SLIGHT
Appearance and Odor:COLORLESS GAS, W/CHARACTERISTIC UNPLEASANT ODOR

=================  Stability and Reactivity Data  =================

Stability Indicator/Materials to Avoid:YES
NATURAL RUBBER/COPPER ALLOY >65%/SILVER/MERCURY/HAALOGEN/ACID/METALLIC
    SODIUM POTASSIUM/POTASSIUM PERMANGANATE MAGNESIUM
Stability Condition to Avoid:IGNITION SOURCES
Hazardous Decomposition Products:ACETYLIDES

====================  Disposal Considerations  ====================

Waste Disposal Methods:DON'T ATTEMPT TO DISPOSE OF WASTE OR UNUSED
    QUANTITIES. RETURN IN THE SHIPPING CONTAINER PROPERLY LABELED,
    W/VALVE PROTECTION CAP IN PLACE TO SUPPLIER FOR PROPER DISPOSAL.
    DISPOSE OF IAW/FEDERAL/STATE /LOCAL REGULATIONS. UN1075. FLAMMABLE
    GAS.

 Disclaimer (provided with this information by the compiling agencies):
 This information is formulated for use by elements of the Department
 of Defense.  The United States of America in no manner whatsoever,
 expressly or implied, warrants this information to be accurate and
 disclaims all liability for its use.  Any person utilizing this
 document should seek competent professional advice to verify and
 assume responsibility for the suitability of this information to their
 particular situation.